Specifications
Absorption chiller, Steam opearted type; Direct-fired type; Hot water type; Flue gas fired type; And etc
Absorption chiller
1. Direct-fired absorption chiller (Double effect)
1). Cooling capacity: 58Kw and above
2). Fuel: Natural gas or diesel oil or BIOS
3). Refrigerator: Water
4). Absorber: Lithium bromide solution
5). Inhibitor: Lithium chromate or Lithium molybdate
2. Steam/vapour-operated absorption chiller (Double or Single effect)
1). Cooling capacity: From 23Kw and above
2). Refrigerator: Water
3). Absorber: Lithium bromide solution
4). Inhibitor: Lithium chromate or Lithium molybdate
5). Working pressure: 0.1 or 0.4 or 0.6 or 0.8MPa
Worthily mentioned, it is single effect when its working pressure is 0.1MPa.
3. Hot water absorption chiller (Double or Single effect)
1). Cooling capacity: From 11.5Kw and above
2). Refrigerator: Water
3). Absorber: Lithium bromide solution
4). Inhibitor: Lithium chromate or Lithium molybdate
Worthily mentioned,
1). Our unit can use hot water from solar to make cool.
2). It could be double effect when its inlet temp is up to 160° C.
4. Flue gas operated absorption chiller (Double or single effect)
1). Cooling capacity: From 58Kw and above
2). Refrigerator: Water
3). Temperature: 200° C and above.
4). Absorber: Lithium bromide solution
5). Inhibitor: Lithium chromate or Lithium molybdate
5. Hot water single effect & Gas fired double effect absorption chiller
1). Cooling capacity: From 35Kw and above
2). Refrigerator: Water
3). Absorber: Lithium bromide solution
4). Inhibitor: Lithium chromate or Lithium molybdate
Worthily mentioned, in such case, the unit could run by hot water only, or gas only, or both by hot water & gas together.
Finally, thanks a lot for your attention and time.
Description |
Small Type Hot Water Absorption Chiller |
Model |
RXZ-115 |
Cooling capacity |
115KW |
Hot water |
Flow rate |
28.5m3/h |
Pressure loss |
80KPa |
Inlet/Outlet Temp |
90/85ºC |
Inlet/Outlet Dia. |
DN65 |
Chilled water |
Flow rate |
20.0m3/h |
Pressure loss |
80KPa |
Inlet/Outlet Temp |
15ºC/10ºC |
Inlet/Outlet Dia. |
DN40 |
Cooling water |
Flow rate |
50.0m3/h |
Pressure loss |
80KPa |
Inlet /outlet Temp |
30ºC/35ºC |
Connection diameter |
DN80 |
Electrical consumption |
0.37kw |
Dimension
|
Length |
2755mm |
Weight |
970mm |
Height |
1990mm |
Shipping weight |
2600kg |
Note:
1. Fouling factor for chilled water and cooling water: 0.086m2ºC/KW.
- The standard gauge pressure limit for chilled water and cooling water:≤0.8Mpa